新聞資訊
聯(lián)系我們
濟(jì)南富強(qiáng)門(mén)業(yè)有限公司
聯(lián)系人:林經(jīng)理
電話(huà):151 6888 2846
郵箱:527800164@qq.com
地址:濟(jì)南市歷下區(qū)化纖廠路8號(hào)3號(hào)樓101號(hào)
濟(jì)南防火卷簾門(mén)的安裝使用的標(biāo)準(zhǔn)是什么?
來(lái)源:http://m.ifxf.cn 日期:2020-09-18 發(fā)布人:
大家在濟(jì)南市場(chǎng)上購(gòu)買(mǎi)了防火卷簾門(mén),在安裝使用的時(shí)候,應(yīng)符合下列規(guī)定:
We have purchased fire-proof rolling shutter doors in Jinan market. When they are installed and used, they should comply with the following requirements:
1 除中庭外,當(dāng)防火分隔部位的寬度不大于30m時(shí),防火卷簾門(mén)的寬度不應(yīng)大于10m;當(dāng)防火分隔部位的寬度大于30m時(shí),防火卷簾門(mén)的寬度不應(yīng)大于該部位寬度的1/3.且不應(yīng)大于20m。
1 except for the central court, when the width of the fire separation part is not more than 30 m, the width of the fire shutter door shall not be more than 10 m; when the width of the fire separation part is greater than 30 m, the width of the fire shutter door shall not be greater than 1 / 3 of the width of the part, and shall not be greater than 20 m.
2 防火卷簾門(mén)應(yīng)具有火災(zāi)時(shí)靠自重自動(dòng)關(guān)閉功能。
2. The fireproof rolling shutter door shall have the function of closing automatically by self weight in case of fire.
3 除《建筑設(shè)計(jì)防火規(guī)范》(GB50016-2014)另有規(guī)定外,防火卷簾門(mén)的耐火極限不應(yīng)低于該規(guī)范對(duì)所設(shè)置部位墻體的耐火極限要求。
3 unless otherwise specified in code for fire protection design of buildings (GB 50016-2014), the fire resistance limit of fireproof rolling shutter door shall not be lower than the fire resistance limit of the wall set in the code.
當(dāng)防火卷簾門(mén)的耐火極限符合現(xiàn)行標(biāo)準(zhǔn)《門(mén)和卷簾的耐火試驗(yàn)方法》GB/T 7633有關(guān)耐火完整性和耐火隔熱性的判定條件時(shí),可不設(shè)置自動(dòng)噴水滅火系統(tǒng)保護(hù)。
When the fire resistance limit of fire rolling shutter door meets the judging conditions of fire integrity and fire insulation in the current national standard fire resistance test methods for doors and rolling shutters (GB / T 7633), automatic sprinkler system protection is not required.
當(dāng)防火卷簾門(mén)的耐火極限僅符合現(xiàn)行標(biāo)準(zhǔn)《門(mén)和卷簾的耐火試驗(yàn)方法》GB/T 7633有關(guān)耐火完整性的判定條件肘,應(yīng)設(shè)置自動(dòng)噴水滅火系統(tǒng)保護(hù)。自動(dòng)噴水滅火系統(tǒng)的設(shè)計(jì)應(yīng)符合現(xiàn)行標(biāo)準(zhǔn)《自動(dòng)噴水滅火系統(tǒng)設(shè)計(jì)規(guī)范》GB50084的規(guī)定,但火災(zāi)延續(xù)時(shí)間不應(yīng)小于該防火卷簾門(mén)的耐火極限。
When the fire resistance limit of fire shutter door only conforms to the current national standard "fire resistance test methods for doors and rolling shutters" GB / T 7633, the judging conditions of fire integrity shall be set up, and automatic sprinkler system shall be set up for protection. The design of automatic sprinkler system should comply with the current national standard code for design of sprinkler systems (GB 50084), but the fire duration should not be less than the fire resistance limit of the fire shutter door.
防火卷簾門(mén)的聯(lián)動(dòng)控制設(shè)計(jì)
Linkage control design of fire shutter door
防火卷簾門(mén)動(dòng)作程序有二步下降和一步下降兩種。
Fire shutter door action procedures have two steps of descent and one step down.
(1)二步下降:疏散通道上設(shè)置的防火卷簾門(mén)的聯(lián)動(dòng)控制設(shè)計(jì)
(1) Two step descent: linkage control design of fire shutter door on evacuation passageway
l 聯(lián)動(dòng)控制方式,防火分區(qū)內(nèi)任兩只獨(dú)立的感煙火災(zāi)探測(cè)器或任一只專(zhuān)門(mén)用于聯(lián)動(dòng)防火卷簾門(mén)的感煙火災(zāi)探測(cè)器的報(bào)警信號(hào)應(yīng)聯(lián)動(dòng)控制防火卷簾門(mén)下降距樓板面1.8m處;
L linkage control mode: the alarm signal of any two independent smoke detectors or any smoke fire detector specially used for linkage fire shutter door in the fire compartment shall control the fire shutter door to drop to 1.8m away from the floor;
任一只專(zhuān)門(mén)用于聯(lián)動(dòng)防火卷簾門(mén)的感溫火災(zāi)探測(cè)器的報(bào)警信號(hào)應(yīng)聯(lián)動(dòng)控制防火卷簾門(mén)下降到樓板面;
The alarm signal of any temperature detector specially used for linkage fire shutter door shall control the fire shutter door to descend to the floor;
在卷簾的任一側(cè)距卷簾縱深0.5m~5m內(nèi)應(yīng)設(shè)置不少于2只專(zhuān)門(mén)用于聯(lián)動(dòng)防火卷簾門(mén)的感溫火災(zāi)探測(cè)器。
No less than 2 temperature sensitive fire detectors specially used for linkage fire shutter door shall be set at any side of the rolling shutter 0.5m ~ 5m deep.
手動(dòng)控制方式,應(yīng)由防火卷簾門(mén)兩側(cè)設(shè)置的手動(dòng)控制按鈕控制防火卷簾門(mén)的升降。
In manual control mode, the lifting of fire shutter door shall be controlled by manual control buttons set on both sides of fire shutter door.
(2)一步下降:非疏散通道上設(shè)置的防火卷簾門(mén)的聯(lián)動(dòng)控制設(shè)計(jì)
(2) One step down: linkage control design of fire shutter door on non evacuation passageway
聯(lián)動(dòng)控制方式,應(yīng)由防火卷簾門(mén)所在防火分區(qū)內(nèi)任兩只獨(dú)立的火災(zāi)探測(cè)器的報(bào)警信號(hào),作為防火卷簾門(mén)下降的聯(lián)動(dòng)觸發(fā)信號(hào),并應(yīng)聯(lián)動(dòng)控制防火卷簾門(mén)直接下降到樓板面。
In the linkage control mode, the alarm signal of any two independent fire detectors in the fire compartment where the fire shutter door is located shall be used as the linkage trigger signal for the fall of the fire shutter door, and the fire shutter door shall be controlled to descend directly to the floor.
手動(dòng)控制方式,應(yīng)由防火卷簾門(mén)兩側(cè)設(shè)置的手動(dòng)控制按鈕控制防火卷簾門(mén)的升降,并應(yīng)能在消防控制室內(nèi)的消防聯(lián)動(dòng)控制器上手動(dòng)控制防火卷簾門(mén)的降落。
The fire shutter can be controlled manually by the fire shutter controller on both sides of the fire door, and the fire shutter can be controlled by manual fire shutter.
閱讀/ Recommended reading
- 電動(dòng)卷簾門(mén)的優(yōu)勢(shì) 2024-11-12
- 濟(jì)南卷簾門(mén):卷簾門(mén)遙控器失靈怎么辦? 2024-09-02
- 濟(jì)南卷簾門(mén)廠:卷簾門(mén)卡主了怎么辦 2024-08-28
- 濟(jì)南電動(dòng)卷簾門(mén):電動(dòng)卷閘門(mén)沒(méi)電了怎么開(kāi)? 2024-08-28
- 濟(jì)南卷簾門(mén):控制器的安裝技巧 2024-07-06
- 車(chē)庫(kù)門(mén)出現(xiàn)故障怎么辦? 2024-06-12
- 防火卷簾門(mén)分幾種類(lèi)別? 2024-06-06
- 防火卷簾門(mén)對(duì)于企業(yè)的使用有哪些? 2024-06-09
濟(jì)南卷簾門(mén):卷簾門(mén)遙控器失靈時(shí)試試本文的方法吧!
2024-11-16
檢查電池 : Check the battery: 檢查遙控器電池是否還有電。如果電池電量不足,更換一節(jié)新的電池即可。在更換電池時(shí),注意電池的正負(fù)極方向,確保放入的電池...